Voltage drop · screening
Check voltage drop on a one-way run.
Drop uses 2 × K × I × D / cm for single-phase and 1.732 for three-phase. K is 12.9 copper and 21.2 aluminum. D is one-way feet.
Calculated results
- Amperes the wire must carry
- 25.0 A
- Wire for those amperes
- 12 AWG
- Wire that also checks drop
- 12 AWG
- Estimated drop
- 6.32 V · 2.63%
- Within the limit
- Yes
What this sheet does
- You enter the load in amps, the voltage, and how far the wire runs. Distance is one way.
- If the load runs for three hours or more, leave the continuous box on. The sheet adds 25% before it picks a wire.
- It finds the smallest wire that can carry those amps.
- It then checks how much voltage that wire loses on the run.
- If the loss is over the limit you set, it steps up to a larger wire until the loss is inside the limit, or until the table runs out.