Article 430 · screening
Size the motor branch circuit.
Use table full-load current for the wire, the breaker, and the disconnect. Use the nameplate amperes for the overload relay. The overload line below uses the table so you can see the percentage. Replace it with the nameplate before you set the relay.
Calculated results
- Table FLC
- 7.6 A
- Minimum conductor amperes, 125%
- 9.5 A
- Suggested conductor
- 14 AWG · 20 A
- Short-circuit device, 250% then next standard
- 20 A
- Calculated device before rounding
- 19 A
- Overload planning value
- 9.5 A
- Disconnect ampere rating, 115%
- 8.7 A
- Voltage drop at table FLC
- 2.07 V · 0.4%
Branch circuit, planning size. The wire and the short-circuit device use table current, not the nameplate. The overload line uses table current so you can see the percentage. Use the nameplate before you set the relay.
What this sheet does
- You pick the motor: one phase or three, the horsepower, and the voltage.
- The sheet looks up that motor’s full-load current in the table. The wire is sized from this number, not from the nameplate.
- It multiplies that current by 1.25. That is the smallest number of amperes the wire must carry.
- It multiplies the same current by the breaker or fuse percent you picked, then rounds up to the next standard size.
- It shows an overload so you can see the percent. Set the real relay from the nameplate amperes, not from this line.
- It checks how many volts you lose over the one-way length you typed.